目的
2
针对医院老旧信息机房不间断电源(uninterruptible power supply, UPS)系统普遍存在的架构缺陷(如无维修旁路、并联冗余失效)和运行风险,探讨在不中断核心业务的前提下,实现紧急故障处置与系统性升级改造的有效模式。
方法
2
首先,通过文献综述梳理了UPS分类及并机方案,明确了老旧系统的主要风险点。其次,以某医院早期建设的无维修旁路、单路输出的并联UPS系统濒临崩溃的极端案例为研究对象,应用风险量化评估方法,决策采用“降载+隔离+热切换”的组合策略。具体技术路径包括:利用服务器双电源特性实施分路降载、通过同源市电创造旁路电压追随条件,并采用“同相电压差并网法”进行带电更换。最后,基于应急经验,设计了一套低投入、高收益的阶段性改造方案。
结果
2
在保障核心业务负载零中断的前提下,成功完成了故障UPS的紧急带电更换。基于此提出的后期改造方案,包括在输入输出端增设独立空气开关、增加维修旁路及铺设市电备用线路,能以较小成本显著提升系统可靠性、安全性与维护便利性。
结论
2
本研究提出的“风险可控的应急带电更换方法”与“低成本阶段性改造框架”,为面临类似老旧基础设施困境的医疗机构提供了一套从应急处理到系统优化的完整解决方案,具有一定的推广应用价值。
Objective
2
This paper addresses the prevalent architectural flaws (e.g., lack of a maintenance bypass, failure of parallel redundancy) and operational risks of uninterruptible power supply (UPS) systems in aging hospital information rooms. It aims to explore effective models for emergency troubleshooting and systematic upgrades without interrupting core business operations.
Methods
2
First, a literature review was conducted to summarize UPS classifications and parallel configurations, identifying key risk points in legacy systems. Second, taking an extreme case of a hospital’s early-stage, non-maintenance-bypass, single-output parallel UPS system on the verge of collapse, a quantitative risk assessment method was applied. A combined strategy of “load reduction, isolation, and hot-swapping” was adopted. Key technical steps included implementing split load reduction using server dual-power supply characteristics, creating a bypass voltage following condition using a common utility power source, and employing an “in-phase voltage differential grid-connection method” for live replacement. Finally, based on the emergency experience, a low-cost, high-impact phased renovation plan was designed.
Results
2
The emergency live replacement of the faulty UPS was successfully accomplished with zero downtime for critical operational loads. The proposed subsequent renovation plan, which included installing independent circuit breakers at UPS input/output ends, adding a maintenance bypass, and laying a backup utility power line, could significantly enhance system reliability, safety, and maintainability at a relatively low cost.
Conclusions
2
The “risk-controlled emergency live replacement method” and the “low-cost phased renovation framework” proposed in this study provide a complete solution ranging from emergency response to systematic optimization for medical institutions facing similar challenges with aging physical infrastructure. This model holds certain value for broader application.
王鑫坤. 加强医院信息机房的安全管理与维护的策略[J]. 电子技术与软件工程, 2019(6): 185.
杨苏敏. 医院信息机房的设计重点[J]. 中国新通信, 2022, 24(1): 11-13.
朱彦斌,刘玉红. 医院网络中心机房UPS的管理与维护[J]. 中国医疗设备, 2010, 25(9): 127-128.
Zhu YB, Liu YH. Management and maintenance of the UPS of the network center computer room[J]. China Medical Devices, 2010, 25(9): 127-128.
程勇,谭碧竹. UPS使用情况调查与日常管理[J]. 中国医学装备, 2008, 5(10): 30-32.
Cheng Y, Tan BZ. Investigation of the usage of UPS and routine management[J]. China Medical Equipment, 2008, 5(10): 30-32.
郭诚刚,管德赛,王宝姣,等. 大型综合医院UPS的日常维护与管理[J]. 江苏卫生事业管理, 2015, 26(3): 143-144.
陈伟. UPS在医院系统中的应用[J]. 智能城市, 2024, 10(10): 43-45.
Chen W. Application of UPS in hospital system[J]. Intelligent City, 2024, 10(10): 43-45.
张倩,王俊俊. UPS在医疗建筑中的应用[J]. 现代建筑电气, 2023, 14(6): 5-8.
Zhang Q, Wang JJ. Application of UPS in medical buildings[J]. Modern Architecture Electric, 2023, 14(6): 5-8.
王彩杰. 关于数据中心机房UPS系统扩容改造的探讨[J]. 电脑知识与技术, 2021, 17(12): 229-230.
Wang CJ. Discussion on capacity expansion and transformation of UPS system in data center computer room[J]. Computer Knowledge and Technology, 2021, 17(12): 229-230.
薛竞翔,郭彦申,杨贵恒,等. UPS电源技术及应用[M]. 北京: 化学工业出版社, 2021: 1-2.
王其英. UPS的发展历史与新技术[J]. 中国金融电脑, 2011(9): 32-36.
管强, 关珊珊. 医疗设备配置UPS不间断电源系统故障解决及维护方案[J]. 中国设备工程, 2022(11): 182-184.
尤骊. 浅谈医院UPS不间断电源安全管理问题及对策建议[J]. 中国设备工程, 2024(2): 68-71.
张腾飞,黄炽雄. 浅谈医院UPS设备风险分析与安全管理[J]. 中国设备工程, 2022(11): 64-65.
王得水,戴建荣,蔡军,等. 基于风险控制的医院UPS电源安全管理与对策研究[J]. 中国医学装备, 2018, 15(6): 137-140.
Wang DS, Dai JR, Cai J, et al. The safety management and countermeasure study for UPS of hospital based on risk control[J]. China Medical Equipment, 2018, 15(6): 137-140.
余诗宝. 医院UPS蓄电池常见问题及应对措施[J]. 中国医院建筑与装备, 2022, 23(2): 79-81.
Yu SB. Common malfunctions and countermeasures of hospital UPS batteries[J]. Chinese Hospital Architecture & Equipment, 2022, 23(2): 79-81.
王玉昆, 王燕妮. 医疗设备不间断供电系统应用研究[J]. 医疗装备, 2011, 24(5): 10-13.
Wang YK, Wang YN. Medical equipment uninterrupted power supply system applied research[J]. Medical Equipment, 2011, 24(5): 10-13.
卜广翔,王俊,郭诚刚,等. 综合性医院UPS选型及运维关键问题探讨[J]. 中国医院建筑与装备, 2024, 25(3): 45-49.
Bu GX, Wang J, Guo CG, et al. Discussion on key issues in UPS selection, operation and maintenance in general hospitals[J]. Chinese Hospital Architecture & Equipment, 2024, 25(3): 45-49.